Filter Fan ATV1101

Filter fan 26 m^3/hr; dimensions 114x114x73mm
Features Unit ATV1101
Air flow rate (free blow) m³/h 26 (30)
Flow rate with exit filter m³/h 15 (18)
Power supply V/Hz 115/50-60
Dimensions HxLxP mm 114x114x73
Power consumption W 13 (12)
Current consumption A 0.14 (0.12)
Overcurrent consumption - impedance
Electric connection - 3-poles spring terminals
Duty cycle - 100%
Operating temperature °C - 10 / +70 (+14 / +158)
Protection degree/class - IP54/Class I
Noise level dB(A) 30 (35)
Flow direction - reversible: default factory setting outside-in
Bearing - ball
Filter mat (Eurovent) - G2
Service life (at 40°C) hr 50 000
Material - ABS UL94V-0 Color RAL7035
Wall thickness mm 1.2-2.4
Gasket - foam seal gasket
Weight (with packaging) kg 0.41 (0.46)
Package dimensions mm 125x125x80
Montaggio - fast clip-on
Conformity/Approvals - CE

 

 

 

Accessories

Filter mat standard type ATVF1
Filter mat high efficiency ATVF1X
Thermostat 0-60°C – NO contact THV2
Fan speed controller FSC
Hood for IP55 CUFF10B